kW to BTU/hr converter (and BTU/hr to kW)
Step 1: quick calculation in 4 answers →Estimate only: floor area, region, insulation and current heating. Final validation afterwards with the full calculator.
kW, BTU/h and tons converter
Type a number in any box. The other two boxes fill in on their own.
kW, BTU/h, ton: the words in plain English
- kW (kilowatt) : a unit of power. It tells how much energy flows at each moment. 1 kW = 1,000 watts. Metric spec sheets use it.
- BTU/h (BTU per hour) : another unit of power. It tells how much heat the unit gives, or removes, in one hour. You may also see BTU/hr or BTUH. It is the most common unit for heat pumps in Canada and the United States.
- Ton : here, it is not a weight. It is a power of 12,000 BTU/h. So a 2-ton heat pump gives 24,000 BTU/h.
The site uses the “IT” BTU, the one in the NIST table: 1 BTU/h = 0.293 071 1 watt. So 1 kW = 1,000 ÷ 0.293 071 1 = 3,412.14 BTU/h (site calculation).
Common heat pump sizes in BTU/h, kW and tons
| BTU/h | kW | Tons |
|---|---|---|
| 9,000 | 2.64 | 0.75 |
| 12,000 | 3.52 | 1 |
| 18,000 | 5.28 | 1.5 |
| 24,000 | 7.03 | 2 |
| 30,000 | 8.79 | 2.5 |
| 36,000 | 10.55 | 3 |
| 48,000 | 14.07 | 4 |
| 60,000 | 17.58 | 5 |
The number on the label, for example “12,000”, is the rated capacity. For heating, it is measured at 8.3 °C (47 °F) (NEEP specification). In deep cold, look at the capacity at −15 °C on the spec sheet instead.
From kW to BTU/h
| kW | BTU/h |
|---|---|
| 1 | 3,412 |
| 2 | 6,824 |
| 3 | 10,236 |
| 4 | 13,649 |
| 5 | 17,061 |
| 6 | 20,473 |
| 7 | 23,885 |
| 8 | 27,297 |
| 10 | 34,121 |
| 12 | 40,946 |
| 15 | 51,182 |
Reading kW and BTU on a spec sheet or the NEEP list
- A spec sheet may give the capacity in BTU/h, in kW, or both. It is the same thing in two units. Convert before you compare two heat pumps.
- Watch out: in the NEEP cold-climate heat pump list, the “kW” row is not the heat delivered. It is the electricity the unit uses. The heat delivered is on the “Btu/h” row (NEEP specification, version 4.0).
- NEEP gives these numbers at 8.3 °C, −8.3 °C and −15 °C (47, 17 and 5 °F), and at the lowest temperature the maker publishes.
- To know how much heat you get for each kW of electricity, convert the BTU/h to kW, then divide by the kW used. This number is called the COP. Example: 24,000 BTU/h = 7.03 kW of heat. If the unit uses 3 kW, the COP is about 2.3 (site calculation).
- Do not mix up kW and kWh. Your Hydro-Québec bill counts kWh: kW used for a number of hours.
Where to look: the NEEP cold-climate heat pump list. To know which numbers to compare, see how to evaluate a heat pump.
What size do I need?
This converter changes units. It does not tell you what size to buy. For the size, start with the guide how many BTU for my house, then do thequick estimate and the heat-loss calculator.
Frequently asked questions
How many BTU/h are in 1 kW?
1 kW = 3,412.14 BTU/h. This comes from the NIST factor: 1 BTU/h = 0.293 071 1 watt.
How many kW is a 12,000 BTU/h heat pump?
About 3.52 kW (12,000 ÷ 3,412.14). It is also 1 ton.
How many BTU/h are in a ton?
12,000 BTU/h, or about 3.52 kW. Here, a ton is a power, not a weight.
Sources
- NIST, Guide for the Use of the International System of Units (SP 811), Appendix B.8 : 1 BTU (IT) per hour = 0.293 071 1 W; 1 ton of refrigeration (12,000 BTU/h) = 3,516.853 W. Checked November 19, 2026.
- NEEP, Cold Climate Air Source Heat Pump Specification, version 4.0 (effective January 1, 2023), and the ccASHP list. Checked November 19, 2026.
See also: how many BTU for my house · heat loss · evaluate a heat pump · all tools.