Quick heat-loss estimate (step 1)

Independent site: no ads, no cookies, no affiliate links. Nothing you enter is sent anywhere: the calculation runs in your browser.

What is your home’s approximate heat loss?

Site calculation: a 1,500 sq ft house with average insulation and no heated basement loses about 24,000–30,000 BTU/h in Montréal (−23 °C) and 26,000–33,000 BTU/h in Québec City (−25 °C). The heat pump should then deliver about 19,000–24,000 BTU/h at −15 °C in Montréal, or be supplemented by backup heat.

How is this estimate calculated?

It reuses the home estimator’s calculation, with no new coefficient: heated area × 16 to 20 BTU/h per sq ft, × climate factor, × insulation factor. The site treats this range as an order of magnitude of the heat loss at the design temperature (site assumption).

Parameters and sources
ParameterValueSource
Base per sq ft16–20 BTU/hTwo Hydro-Québec benchmarks: 12,000 BTU/h per 750 sq ft (determining capacity) and 15,000 BTU/h per 750 sq ft (seven points to consider).
Heated areaabove basement + heated basementSame per-sq-ft rule applied to the heated basement; the full calculator handles below-grade walls separately.
Climate factor1 + 0,5 × (DJ ÷ 4 363 − 1)ECCC degree-days for the location, as on thehome estimator; weighting: site estimate.
Insulation factor0,9 · 1 · 1,15Site estimate (good, average, poor), same as the home estimator.
Design temperatureJanuary 2.5%NBC 2020, Table C-2 (see Québec design temperatures). Beauce: location not listed, no value estimated.
Capacity at −15 °C and −25 °C× (60 − T °F) ÷ (60 − design T °F)Equation 4 of the NRCan sizing guide (load proportional to the difference from 15.6 °C), applied by the site at −15 °C and −25 °C.

What is the heat loss of a 1,500 sq ft house?

Results of the calculation above, rounded to the nearest 1,000 BTU/h. At −25 °C, the capacity to look for exceeds the design heat loss when the location’s design temperature is milder than −25 °C.

1,500 sq ft house above the basement, average insulation, no heated basement (site calculation)
LocationDesign temperatureDesign heat loss (BTU/h)Capacity to look for at −15 °C (BTU/h)Capacity to look for at −25 °C (BTU/h)
Montréal (City Hall)−23 °C24,000–30,00019,000–24,00025,000–32,000
Québec−25 °C26,000–33,00020,000–25,00026,000–33,000
Saguenay (Bagotville)−31 °C28,000–34,00018,000–22,00024,000–30,000
Sept-Îles−29 °C29,000–36,00020,000–25,00026,000–33,000
Montréal, 1,500 sq ft above the basement: effect of insulation and basement (site calculation)
HouseDesign heat loss (BTU/h)Capacity to look for at −15 °C (BTU/h)Capacity to look for at −25 °C (BTU/h)
Recent or renovated (good insulation)22,000–27,00017,000–21,00023,000–28,000
Average insulation24,000–30,00019,000–24,00025,000–32,000
Older, poorly insulated28,000–35,00022,000–28,00029,000–37,000
Average insulation + 750 sq ft heated basement36,000–45,00029,000–36,00038,000–47,000

What should you do after this first estimate?

  1. Validate with the heat-loss calculator (walls, windows, ceiling, basement, air leakage).
  2. Compare models with the guide how to evaluate a heat pump : capacity at −15 °C and −25 °C, COP, HSPF2, official lists.
  3. Have the sizing with a CSA F280 calculation by an RBQ-licensed contractor.

Frequently asked questions

Why two calculators?

This one gives an order of magnitude from four answers, based on floor area. The heat-loss calculator adds up walls, windows, ceiling, basement and air leakage, level by level: it is the final check before comparing models.

Where do the capacities at −15 °C and −25 °C come from?

From equation 4 of NRCan’s sizing guide, which assumes a load proportional to the difference between 15.6 °C (60 °F) and the outdoor temperature. The guide applies it at −8.3 °C; the site applies it at −15 °C and −25 °C, two temperatures where manufacturers and the NEEP list publish data.

Is my data sent anywhere?

No. The calculation runs in your browser and nothing you enter is transmitted.

Sources

Step 2: full heat-loss calculator →
How to evaluate a heat pump →